iSMA-B-12O-H-IP - 12 relay outputs
- 24 digital relay outputs
- Communication: BACnet MS/TP, Modbus ASCII/RTU
- Manual Override Switches
- Simplified Configuration and Commissioning Process
GET A QUOTE: ampero@ampero.eu
Description
MAX-IO - Product Brochure
iSMA-B-MAX-IP - Datasheet
iSMA-B-MAX-IP - Karta katalogowa
Multiprotocol I/O Modules Bacnet - Manual
Multiprotocol I/O Modules Modbus - Manual
Multiprotocol I/O Module with a MAX number of Digital Outputs - a powerful addition to any building automation system
Digitalize buildings with reduced engineering time using the powerful 12 digital outputs module, which works as a remote I/O over IP with open protocols, BACnet IP and Modbus TCP/IP. Open protocols standard offers the versatility of installing the modules in both new and existing facilities, whether it is a system expansion or a retrofit. The maximum number of the most popular types of inputs or outputs allows the module to be a versatile controller extension, whether in a small or large facility.
12 relay outputs
Digital outputs equipped with normally open 3 A relays allow for direct control without additional relays.
Manual Override Switches
Each output can be manually overridden using a dedicated hand-operating switch.
Modbus TCP/IP to Modbus RTU/ASCII Gateway
Built-in Modbus gateway on the COM1 port enables integration of up to 128 Modbus slave devices to the IP layer.
Simplified Configuration and Commissioning Process
The module allows for seamless configuration over BACnet, Modbus, built-in web server, or dedicated free of charge tool. The ability to be powered from a USB port facilitates local testing and a straightforward updating process. Two Ethernet ports working in a switch mode allow for daisy chaining of multiple modules over the RJ45, which facilitates the cabling process and reduces engineering time.
Quality and Reliability Confirmed by Certificates
iSMA CONTROLLI is a long-standing member of the BACnet community. The experience in developing high quality products and the BTL (BACnet Test Laboratory) certification confirms the excellent performance of communication using the BACnet protocol.
TECHNICAL SPECIFICATION
HARDWARE:
- 2 Ethernet interface with built-in switch
- RS485 interface
- miniUSB type B interface
- Status LED indicator
- DIN rail mounted
- Hand-off-auto switches
- 12 relay outputs
OUTPUTS
- 12 relay outputs
- NO relay outputs
- Resistive load max. 3 A @ 230 V AC / 30 V DC
- Inductive load max. 75 VA @ 230 V AC / 30 W @ 30 V DC
COMMUNICATION
- BACnet IP
- Modbus TCP/IP
- Modbus TCP/IP to Modbus RTU/ASCII Gateway
- Free software iSMA Configurator
- Dedicated Niagara Framework modules
POWER SUPPLY
- 24 V DC ± 20%
- 24 V AC ± 20%
Related products