iSMA-B-MIX38-IP - 38 inputs / outputs digital and analog
- 8 universal inputs: temperature, analog, digital dry contact inputs
- 12 digital inputs, dry contact inputs
- 12 relay outputs
- 6 analog outputs 0-10VDC
- Communication: BACnet IP, Modbus TCP/IP
- Modbus TCP/IP to Modbus RTU/ASCII Gateway
GET A QUOTE: ampero@ampero.eu
Description
iSMA-B-MIX-IP - Datasheet
iSMA-B-MIX-IP - Karta katalogowa
Multiprotocol I/O Modules Bacnet - Manual
Multiprotocol I/O Modules Modbus - Manual
Multiprotocol Module with a MIX of I/O's - the Ultimate Controller Extension
Powerful I/O module that works as a remote or distributed I/O over IP with open protocols, BACnet IP and Modbus TCP/IP. Open protocol standard offers the versatility of installing the modules in both new and existing facilities, whether it is a system expansion or a retrofit. The most popular types of inputs and outputs are MIXed in a space-saving design and allow the module to be a versatile controller extension, whether in a small or large facility.
8 Universal Inputs
Support for over 20 types of temperature sensors and voltage, resistance, current, and dry contact measurements on each universal input.
12 Digital Inputs
Dry contact inputs - made for monitoring. 100 Hz fast pulse counter with override function saves the real-time values to the EEPROM memory.
12 Digital Outputs
Digital outputs equipped with normally open 3 A relays allow for a direct control without additional relays.
6 Analog Outputs
0-10 V DC control with 10 mA accuracy, PWM modes, and a maximum load of up to 20 mA to power external relays makes the output suitable for a variety of scenarios.
Modbus TCP/IP to Modbus RTU/ASCII Gateway
Built-in Modbus gateway on the COM1 port enables integration of up to 128 Modbus slave devices to the IP layer.
Simplified Configuration and Commissioning Process
The module allows for seamless configuration over BACnet, Modbus or dedicated free of charge tool. The ability to be powered from a USB port facilitates local testing and a straightforward updating process, and the high-end RS485 transceiver allows up to 128 devices to communicate reliably with the client on a single bus.
Quality and Reliability Confirmed by Certificates
iSMA CONTROLLI is a long-standing member of the BACnet community. The experience in developing high quality products and the BTL (BACnet Test Laboratory) certification confirm the excellent performance of communication using the BACnet protocol.
TECHNICAL SPECIFICATION
HARDWARE:
- 2 Ethernet ports with built-in switch
- RS485 interface
- miniUSB type B interface
- Status LED indicator
- DIN rail mounted
- 8 universal inputs, dry contact inputs
- 12 digital inputs, dry contact inputs
- 12 relay outputs
- 6 analog outputs, 0-10VDC
INPUTS
- 8 universal inputs:
- temperate: 10K3A1, 10K4A1, Carel 10K, 20K6A1, 2.2K3A1, 3K3A1, 30K6A1, SIE1, TAC1, SAT1, Pt1000, Ni1000 0C, Ni 1000 20C, Ni1000 LG
- resistive: 0-1000 kΩ
- voltage: 0-10 VDC
- current: 0-20mA
- digital: dry contact - 12 digital inputs
- dry contact inputs
- Fast pulse counter up to 100 Hz saved in EEPROM memory
OUTPUTS
- 6 analog outputs 0-10VDC
- accuracy 10mA
- maximum load up to 20 mA
-PWM: 0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz, 100 Hz - 12 relay outputs
- NO relay outputs
- Resistive load max. 3 A @ 230 V AC / 30 V DC
- Inductive load max. 75 VA @ 230 V AC / 30 W @ 30 V DC
COMMUNICATION
- BACnet IP
- Modbus TCP/IP
- Modbus TCP/IP to Modbus RTU/ASCII Gateway
- Free software iSMA Configurator
- Dedicated Niagara Framework modules
POWER SUPPLY
- 24 V DC ± 20%
- 24 V AC ± 20%